Weekly Inspection

As per CSA Standards (C282-15 Clause 11.4 – table 2) during a weekly inspection the consumables, starter system, batteries, charging equipment, engine, control panel and air control louver settings receive thorough inspection and testing where applicable to ensure proper levels and operation. The emergency lights are tested and the temperature of the generator room must be verified as above 10 degrees Celsius. Upon inspection and testing, all defects found are to be corrected. A record of the weekly inspection, testing and corrective actions are to be recorded in the log (see C282-15 Clause 11.5.3.).